We’re moving! Schaffner is now part of TE Connectivity.
Dear Users, The Schaffner website will transition to TE.com. Starting January 7th 2026, please visit TE.com for all product details, request samples, place orders, and support. If you experience any issue or have additional question, feel free to reach us at customercare-ibte.com

Legacy Products FN3416

Ecosine 400-480 VAC 50Hz Economy Passive Harmonic Filters

FN3416

Ecosine 400-480 VAC 50Hz Economy Passive Harmonic Filters

  • Economy line of passive harmonic filters for THDi <10%
  • Help to comply with EN 61000-3-12, IEEE-519 and other PQ standards
  • Support an efficient utilization of electrical system capacity
  • Ideal for motor drives with 6-pulse rectifier front-end
  • Suitable for diode and thyristor (SCR) rectifiers applications

Features and Benefits

FN3416 (50 Hz) models of the ECOsine product family represent the very compact economy line with a THID performance of >10% (with Ldc).

They are ideal for non-linear three-phase equipment with B6 rectifier front-end that do not require the industry leading <5% THID performance provided by Schaffner Ecosine Evo series.

The performance is still sufficient to comply with EN 61000-3-12 or with IEEE-519 for Isc/IL <50. Schaffner Ecosine filters help to unburden the electrical infrastructure from excess loading and heat caused by current harmonics, and therefore support a better utilization of electric system capacity.

Lower harmonics also reduce the risk of system resonances and potential downtime of sensitive electronic equipment.

FN3416/18 filters upgrade standard motor drives to low-harmonic drives quickly and easily.

Typical Applications

Three-phase power conversion equipment with front-end six-pulse rectifier (diode or SCR)
Motor drives, like those used e.g. in pump and fan applications
Battery chargers, incl. DC fast chargers for e-cars

Technical Specifications

Nominal operating voltage

3x380 to 500 VAC ±10%

Overload capability

1.6x rated current for 1 minute, once per hour

Operating frequency

50Hz ±1 Hz (FN 3416)

Total harmonic current distortion THDi*

<10% @ rated power (with DC-Link choke)

<15% @ rated power (without DC-Link choke)

Total demand distortion TDD

According to IEEE-519

Nominal motor drive input power rating

4 to 160 kW

High potential test voltage

P -> E 2500 VAC (2 sec)

Earthing system

TN, TT, IT

Efficiency

>98% @ nominal line voltage and power

Temperature range (operation and storage)

–25°C to +45°C fully operational

+45°C to +70°C derated operation***

–25°C to +70°C transport and storage

Cooling

Internal fan cooling, unregulated

Protection category

IP 20

Flammability corresponding to

UL 94 V-0

Design corresponding to

UL 508, EN 61558-2-20, CE (LVD2006/95/EC)

SCCR**

100 kA

* System requirements: THVD <2%, line voltage unbalance <1% Note: performance specifications in this datasheet refer to six-pulse diode rectifiers. SCR rectifier front-end will produce different results, depending upon the firing angle of the thyristors. ** External UL-rated fuses required. *** Iderated = Inominal*SQRT(70°C-Tamb)/25°C

Typical electrical schematic

FN3416

Approvals & Compliances

CE Label
UKCA Label
RoHS Label
UL Listed USA Label