DATASHEET
Ecosine evo (5% THDi) FN 3452
Ecosine evo, 60 Hz passiver Oberschwingungsfilter
2021
21 Jun 2021
Ecosine passiv
FN 3452: Ecosine evo, 60 Hz passiver Oberschwingungsfilter
  • Der Industriestandard für 6-Puls-Gleichrichter und Motorantriebe
  • Filter für Diodengleichrichter mit Zwischenkreisdrossel
  • Erstklassige Teillastleistung
  • Kompakteste Bauform
  • Plug and Play, gebrauchsfertig
Technical specifications

Nominal operating voltage

3 x 440 VAC to 480 VAC ±10%

Frequenz

60 Hz ±1 Hz

Nominal motor drive input power rating

1.5 to 300 HP

Total harmonic current distortion THDi*

<5% at rated power

Efficiency

>98% for rated voltage and power

Overload capability

1.6x rated current for 1 minute, once per hour

SCCR**

100 kA

High potential test voltage

P –> E 2160 VAC (1 s)

Overvoltage category

OV III (IEC 60664-1 / UL 61800-5-1)

Earthing System

TN, TT, IT

Protection category

IP 00, IP 20

Cooling

Internal fan cooling or external cooling***

Ambient temperature range

–25°C to +45°C fully operational
+45°C to +70°C derated operation****
–25°C to +85°C transport and storage

Design corresponding to

Filter: UL 61800-5-1, EN 61800-5-1
Chokes: EN 61558-2-20 or EN 60076-6

Flammability corresponding to

UL 94 V-2

MTBF @ 45°C/480 V (Mil-HB-217F)

>200,000 hours

Approvals & Compliances

(abhängig von der Filterkonfiguration)

Features and benefits

Schaffner ecosine harmonic filters represent an economical solution to the challenge of load-applied harmonics mitigation in three-phase power systems. With a plug-and-play approach and more compact dimensions than comparable products, they can be quickly installed and easily commissioned. They increase the reliability and service life of electric installations, help utilize electric sytem capacity better, and are the key to meet Power Quality standards such as IEEE 519. Ecosine filters reshape your distorted current back to the desired sinusoidal waveform. Schaffner ecosine filters can be applied to virtually any kind of power electronics with front-end six-pulse rectifiers, 3-phase diode or thyristor bridges, where harmonic current distortion needs to be reduced to defined limits.

Typical applications

  • Equipment with front-end six-pulse rectifier
  • Motor drives
  • Factory automation equipment
  • Water/wastewater treatment facilities
  • Fan and pump applications
  • HVAC installations
  • Mission-critical processes
  • DC fast chargers

Typical electrical schematic

(all configurable optional functionalities shown)

Filter selection table @ 480 V / 60 Hz – IP 00 enclosure

Filter

Rated load power

Motor driveRated filterWeight


Typical
TerminalFrame 

@ 480 V/60 Hz

input currentinput currentlossessize

[kW]

[HP]

[Arms]***[Arms]

[kg]

[lbs][W]****
FN 3452-1-110-E0_ _ _ _ _*1.11.521.3761350110A
FN 3452-3-110-E0_ _ _ _ _*2.2342.7681867110A
FN 3452-5-112-E0_ _ _ _ _*3.7574.571022116112B
FN 3452-8-112-E0_ _ _ _ _*5.67.5116.911329132112B
FN 3452-10-112-E0_ _ _ _ _*7.510149.291635160112C
FN 3452-15-112-E0_ _ _ _ _*11152113.81840237112C
FN 3452-20-113-E0_ _ _ _ _15202718.52760294113D
FN 3452-25-113-E0_ _ _ _ _19253423.13168351113D
FN 3452-30-113-E0_ _ _ _ _22304427.83679354113D
FN 3452-40-115-E0_ _ _ _ _30405237.246101459115E
FN 3452-50-115-E0_ _ _ _ _37506646.251112571115E
FN 3452-60-115-E0_ _ _ _ _45608355.659130589115E
FN 3452-75-115-E0_ _ _ _ _567510369.360132821115F
FN 3452-100-115-E0_ _ _ _ _7510012892.5821811028115F
FN 3452-125-116-E0_ _ _ _ _931251651151162561067116G
FN 3452-150-116-E0_ _ _ _ _1121502081391373021143116G

FN 3452-200-118-E0_ _ _ _ _

1492002401841703751538118H

FN 3452-250-118-E0_ _ _ _ _**

1862503202311874121411118H
FN 3452-300-118-E0_ _ _ _ _**2243004032792525561775118H

*      Filter rating which does not require forced cooling or fan module
**    Filter rating which does not require RC damping module for rectifiers with EMI filter
***  Motor drive input current without harmonic filter
**** Typical losses @ 45°C, 480V, 60Hz and rated load power

Filter power terminals

Terminal designation*

Screw thread

Flex wire AWGFlex wireScrew torque value


Max width**Frame size
cable lug
[mm2]  [Nm][lbs·in][mm]
110M314-220.4-2.50.54.47A
112M410-220.4-61.210.610B, C
113M66-180.75-16326.615D
115M81/0-810-50870.815E, F
116M83/0-810-95870.817G
118M103/0-500 kcmil95-2401088.535H

*  Recommended connector type: wire or cable lug for 110 to 113, only cable lug for 115 to 118
** To fulfill creepage/clearance acc. UL 61800-5-1 without additional protection (insulation). Creepage/clearance can vary depending on applicable standard and must be reviewed by customer. Creepage/clearance may be reduced when additional protection (insulation) is provided.

Filter signal and earth terminals

Terminal type

Screw thread

Screw torque value


Frame size
  [Nm][lbs·in]
SignalM3*0.54.4All
Earth (PE)M52.219.5A
Earth (PE)M6435.4B, C
Earth (PE)M8979.7D, E
Earth (PE)M1017150.5F, G, H

* Max width cable lug = 7 mm

Filter selection table @ 480 V / 60 Hz – IP 20 enclosure

Filter

Rated load power

Motor driveRated filterWeight

TypicalTerminalFrame 

@ 480 V/60 Hz

input currentinput currentlossessize

[kW]

[HP]

[Arms]***[Arms]

[kg]

[lbs][W]****
FN 3452-1-110-E2_ _ _ _ _*1.11.521.3771550110A
FN 3452-3-110-E2_ _ _ _ _*2.2342.7692067110A
FN 3452-5-112-E2_ _ _ _ _*3.7574.571124116112B
FN 3452-8-112-E2_ _ _ _ _*5.67.5116.911431132112B
FN 3452-10-112-E2_ _ _ _ _*7.510149.291737160112C
FN 3452-15-112-E2_ _ _ _ _*11152113.82044237112C
FN 3452-20-113-E2_ _ _ _ _15202718.53168294113D
FN 3452-25-113-E2_ _ _ _ _19253423.13577351113D
FN 3452-30-113-E2_ _ _ _ _22304427.84088354113D
FN 3452-40-115-E2_ _ _ _ _30405237.252115459115E
FN 3452-50-115-E2_ _ _ _ _37506646.257126571115E
FN 3452-60-115-E2_ _ _ _ _45608355.665143589115E
FN 3452-75-115-E2_ _ _ _ _567510369.367148821115F
FN 3452-100-115-E2_ _ _ _ _7510012892.5901981028115F
FN 3452-125-116-E2_ _ _ _ _931251651151252761067116G
FN 3452-150-116-E2_ _ _ _ _1121502081391463221143116G

FN 3452-200-118-E2_ _ _ _ _

1492002401841874121538118H

FN 3452-250-118-E2_ _ _ _ _**

1862503202312044501411118H
FN 3452-300-118-E2_ _ _ _ _**2243004032792695931775118H

*      Filter rating which does not require forced cooling or fan module
**    Filter rating which does not require RC damping module for rectifiers with EMI filter
***  Motor drive input current without harmonic filter
**** Typical losses @ 45°C, 480V, 60Hz and rated load power

Filter power terminals

Terminal designation*

Screw thread

Flex wire AWGFlex wireScrew torque value


Max width**Frame size
cable lug
[mm2]  [Nm][lbs·in][mm]
110M314-220.4-2.50.54.47A
112M410-220.4-61.210.610B, C
113M66-180.75-16326.615D
115M81/0-810-50870.815E, F
116M83/0-810-95870.817G
118M103/0-500 kcmil95-2401088.535H

*  Recommended connector type: wire or cable lug for 110 to 113, only cable lug for 115 to 118
** To fulfill creepage/clearance acc. UL 61800-5-1 without additional protection (insulation). Creepage/clearance can vary depending on applicable standard and must be reviewed by customer. Creepage/clearance may be reduced when additional protection (insulation) is provided.

Filter signal and earth terminals

Terminal type

Screw thread

Screw torque value


Frame size
  [Nm][lbs·in]
SignalM3*0.54.4All
Earth (PE)M52.219.5A
Earth (PE)M6435.4B, C
Earth (PE)M8979.7D, E
Earth (PE)M1017150.5F, G, H

* Max width cable lug = 7 mm

Product selector

Table 1: Filter configurations if external air flow is available for cooling

(Filters do not contain fan and do not contain aux. power supply)

E0XXXXX

- For rectifiers without DC-link
  choke



E0XXJXX

- For rectifiers without DC-link
  choke

- Filters contain trap disconnect
  jumper

E0XXXRX

- For rectifiers without DC-link
  choke and with EMI filter

- Filters contain RC damper
  module

E0XXJRX

- For rectifiers without DC-link 
  choke and with EMI filter

- Contain RC damper module
  and trap disconnect jumper

Table 2: Filter configurations with embedded ventilation

(Filters contain fan and aux. power supply)

E0FAXXX and E2FAXXX

- For rectifiers without DC-link
  choke

- Filters contain fan, aux. power
  supply

E0FAJXX and E2FAJXX

- For rectifiers without DC-link
  choke

- Filters contain fan, aux. power
  supply and trap disconnect
  jumper

E0FAXRX and E2FAXRX

- For rectifiers without DC-link
  choke and with EMI filter

- Filters contain fan, aux. power
  supply and RC damper module
 

E0FAJRX and E2FAJRX

- For rectifiers without DC-link
  choke and with EMI filter

- Filters contain fan, aux. power
  supply, RC damper module and
  trap disconnect jumper

Table 3: Filter configurations if external aux. power supply for the fan is available

(Filters contain fan but do not contain aux. power supply, user should provide aux. power supply to the fan)

E0FXXXX and E2FXXXX

- For rectifiers without DC-link
  choke

- Filters contain fan
  

E0FXJXX and E2FXJXX

- For rectifiers without DC-link
  choke

- Filters contain fan and trap
  disconnect jumper

E0FXXRX and E2FXXRX

- For rectifiers without DC-link
  choke and with EMI filter

- Filters contain fan and RC
  damper module

E0FXJRX and E2FXJRX

- For rectifiers without DC-link
  choke and with EMI filter

- Contain fan, RC damper module
  and trap disconnect jumper

Mechanical data of IP 00 enclosure

Frame sizes A-F

Frame sizes G and H

Dimensions

Dimensions in [mm]Dimensions in [in]

Frame

Drill pattern

BaseVolumeDrill patternBaseVolume

R

STUXYZRSTUXYZ
A340120736030216018513.44.70.314.211.96.37.3
B405120742537018020615.94.70.316.714.67.18.1
C460150748343021022118.15.90.319.016.98.38.7
D5401801156049126025221.37.10.422.019.310.29.9
E6802201170563529031926.88.70.427.825.011.412.6
F7302501175268434034328.79.80.429.626.913.413.5
G9202801196086335338636.211.00.437.834.013.915.2
H1115390111150105346245643.915.40.445.341.518.218.0

Inlet air flow required for cooling

Frame size

Min air volume*

[m3/h]CFM [ft3/min]
A, B, C00
D12875
E204120
F, G408240
H612360

* External air flow required for filter configurations without embedded
   ventilation

Mechanical data of IP 20 enclosure

Frame sizes A-D

Frame sizes E-H

Dimensions

Dimensions in [mm]Dimensions in [in]

Frame

Drill pattern

BaseVolumeDrill patternBaseVolume

R

STUXYZRSTUXYZ
A340120736030216018513.44.70.314.211.96.37.3
B405120742537018020615.94.70.316.714.67.18.1
C460150748343021022118.15.90.319.016.98.38.7
D5401801156049126025221.37.10.422.019.310.29.9
E6802201170563529031926.88.70.427.825.011.412.6
F7302501175268434034328.79.80.429.626.913.413.5
G9202801196086335338636.211.00.437.834.013.915.2
H1115390111150105346245643.915.40.445.341.518.218.0

Inlet air flow required for cooling

Frame size

Min air volume*

[m3/h]CFM [ft3/min]
A, B, C00
D12875
E204120
F, G408240
H612360

* External air flow required for filter configurations without embedded
   ventilation

Headquarters, global innovation and development

Switzerland
Schaffner Group
Industrie Nord
Nordstrasse 11e
4542 Luterbach
T +41 32 681 66 26
info@schaffner.com

www.schaffner.com

© 2021 Schaffner Group

The content of this document has been carefully checked and understood. However, neither Schaffner nor its subsidiaries assume any liability whatsoever for any errors or inaccuracies of this document and the consequences thereof. Published specifications are subject to change without notice. Product suitability for any area of application must ultimately be determined by the customer. In all cases, products must never be operated outside their published specifications. Schaffner does not guarantee the availability of all published products. This disclaimer shall be governed by substantive Swiss law and resulting disputes shall be settled by the courts at the place of business of Schaffner Holding AG. Latest publications and a complete disclaimer can be downloaded from the Schaffner website. All trademarks recognized.

PQ sales

Switzerland
Schaffner Power Quality
Nordstrasse 11e
4542 Luterbach
T +41 32 681 66 80
pqsales@schaffner.com

China
Schaffner Power Quality China
T20-3 C, No 565 Chuangye Road
Pudong district
201201 Shanghai
T 021-38139500-2412
pqsales@schaffner.com

Singapore
Schaffner Power Quality APAC
#05-09, Kg Ubi Ind. Estate
Blk 3015A Ubi Road 1
408705 Singapore
T +65 6460 4166
pqsales@schaffner.com