DATASHEET
Evo line (5% THID) FN 3443
Ecosine evo, 60 Hz passiver Oberschwingungsfilter
2019
05 Jul 2019
Ecosine passiv
FN 3443: Ecosine evo, 60 Hz passiver Oberschwingungsfilter
  • Der Industriestandard für 6-Puls-Gleichrichter und Motorantriebe
  • Filter für Diodengleichrichter mit Zwischenkreisdrossel
  • Erstklassige Teillastleistung
  • Kompakteste Bauform
  • Plug and Play, gebrauchsfertig
Technical specifications

Nominal operating voltage

3x380 VAC to 415 VAC ± 10%

Frequenz

60 Hz ±1 Hz

Nominal motor drive input power rating

1 to 240 HP

Total harmonic current distortion THID*

<5% at rated power

Efficiency

>98% for rated voltage and power

Protection category

IP 00, IP 20*****

Cooling

Internal fan cooling or external cooling**

Overload capability

1.6x rated current for 1 minute, once per hour

Ambient temperature range

–25°C to +45°C fully operational
+45°C to +70°C derated operation***
–25°C to +85°C transport and storage

Flammability corresponding to

UL 94 V-2

Design corresponding to

Filter: UL 61800-5-1, EN 61800-5-1
Chokes: EN 61558-2-20 or EN 60076-6

MTBF @ 45°C/480 V (Mil-HB-217F)

>200,000 hours

SCCR****

100 kA

Earthing System

TN, TT, IT

Approvals

(depending on filter configuration)

Features and benefits

Schaffner ecosine harmonic filters represent an economical solution to the challenge of load-applied harmonics mitigation in three-phase power systems. With a plug-and-play approach and more compact dimensions than comparable products, they can be quickly installed and easily commissioned. They increase the reliability and service life of electric installations, help utilize electric sytem capacity better, and are the key to meet Power Quality standards such as IEEE 519. Ecosine filters reshape your distorted current back to the desired sinusoidal waveform. Schaffner ecosine filters can be applied to virtually any kind of power electronics with front-end six-pulse rectifiers, 3-phase diode or thyristor bridges, where harmonic current distortion needs to be reduced to defined limits.

Typical applications

  • Equipment with front-end six-pulse rectifier
  • Motor drives
  • Factory automation equipment
  • Water/wastewater treatment facilities
  • Fan and pump applications
  • HVAC installations
  • Mission-critical processes
  • DC fast chargers

Typical electrical schematic

(all configurable optional fuctionalities shown)

Filter selection table @ 380 V / 60 Hz – IP 00 enclosure

Filter

Rated load power

Motor driveRated filterMin. requiredMin. requiredWeight

TypicalTerminalFrame

@ 380V/60 Hz

input currentinput currentLDCLAClossessize

[kW]

[HP]

[Arms]***[Arms][mH]*****[mH]*****

[kg]

[lbs][W]****
FN 3443-1-110-E0_ _ _ _ _*0.91.21.41.3721.49511.60751141110A
FN 3443-2-110-E0_ _ _ _ _*1.72.42.92.7418.2076.145715.453110A
FN 3443-4-112-E0_ _ _ _ _*2.94.04.84.5210.6733.602919.888112B
FN 3443-6-112-E0_ _ _ _ _*4.46.07.26.857.0352.3741226.5101112B
FN 3443-8-112-E0_ _ _ _ _*5.98.09.69.25.2461.77113.630123112C
FN 3443-12-112-E0_ _ _ _ _*8.712.014.413.73.5581.2011635.3183112C
FN 3443-16-113-E0_ _ _ _ _11.916.019.318.32.6060.8802350.7228113D
FN 3443-20-113-E0_ _ _ _ _15.020.024.0232.0630.6962657.3277113D
FN 3443-24-113-E0_ _ _ _ _17.424.029.027.51.7790.6003066.1282113D
FN 3443-32-115-E0_ _ _ _ _23.832.038.536.81.3010.4343781.6370115E
FN 3443-40-115-E0_ _ _ _ _29.340.048.045.81.0560.3574292.6453115E
FN 3443-48-115-E0_ _ _ _ _35.648.058.0550.8690.29348105.8476115E
FN 3443-60-115-E0_ _ _ _ _44.360.072.0690.6990.23649108634115F
FN 3443-80-115-E0_ _ _ _ _59.480.097.0920.5210.17668150779115F
FN 3443-100-116-E0_ _ _ _ _73.6100.0120.01140.4210.14297214788116G
FN 3443-120-116-E0_ _ _ _ _88.7120.0144.01380.3490.118113250831116G

FN 3443-160-118-E0_ _ _ _ _

118.0160.0192.01830.2620.0891383041199118H

FN 3443-200-118-E0_ _ _ _ _**

147.3200.0240.02290.2100.0711523351022118H
FN 3443-240-118-E0_ _ _ _ _**177.3240.0290.02770.1750.0592054521292118H

*        Filter rating which does not require forced cooling or fan module
**      Filter rating which does not require RC damping module for rectifiers with EMI filter
***    Motor drive input current without harmonic filter
****  Typical losses @ 45°C, 380V, 60Hz and rated load power
***** In order to apply FN 3443 filters, motor drives have to be equipped with either DC-link choke or AC line choke. The minimum required inductance values are given in mH in the filter selection table. If neither DC-link choke nor AC line choke is present, or if the minimum mH rating is not fulfilled, FN 3443 filter must not be used. In this case, FN 3442 need to be chosen.

Filter power terminals

Terminal designation*

Screw thread

Flex wire AWGFlex wireScrew torque value


Max width**Frame size
cable lug
[mm2]  [Nm][lbs·in][mm]
110M314-220.4-2.50.54.47A
112M410-220.4-61.210.610B, C
113M66-180.75-16326.615D
115M81/0-810-50870.815E, F
116M83/0-810-95870.817G
118M103/0-500 kcmil95-2401088.535H

*  Recommended connector type: wire or cable lug for 110 to 113, only cable lug for 115 to 118
** To fulfill creepage/clearance acc. UL 61800-5-1 without additional protection (insulation). Creepage/clearance can vary depending on applicable standard and must be reviewed by customer. Creepage/clearance may be reduced when additional protection (insulation) is provided.

Filter signal and earth terminals

Terminal type

Screw thread

Screw torque value


Frame size
  [Nm][lbs·in]
SignalM3*0.54.4All
Earth (PE)M52.219.5A
Earth (PE)M6435.4B
Earth (PE)M6435.4C
Earth (PE)M8979.7D
Earth (PE)M8979.7E
Earth (PE)M1017150.5F
Earth (PE)M1017150.5G
Earth (PE)M1017150.5H

* Max width cable lug = 7 mm

Filter selection table @ 380 V / 60 Hz – IP 20 enclosure

Filter

Rated load power

Motor driveRated filterMin. requiredMin. requiredWeight

TypicalTerminalFrame

@ 380 V/60 Hz

input currentinput currentLDCLAClossessize

[kW]

[HP]

[Arms]***[Arms][mH]*****[mH]*****

[kg]

[lbs][W]****
FN 3443-1-110-E2_ _ _ _ _*0.91.221.421.49511.607715.441110A
FN 3443-2-110-E2_ _ _ _ _*1.72.442.718.2076.145919.853110A
FN 3443-4-112-E2_ _ _ _ _*2.9474.610.6733.6021124.388112B
FN 3443-6-112-E2_ _ _ _ _*4.46.116.97.0352.3741431101112B
FN 3443-8-112-E2_ _ _ _ _*5.98149.45.2461.77117.438123112C
FN 3443-12-112-E2_ _ _ _ _*8.7122113.83.5581.2012044183112C
FN 3443-16-113-E2_ _ _ _ _11.9162918.82.6060.8803168228113D
FN 3443-20-113-E2_ _ _ _ _15.0203624.02.0630.6963577277113D
FN 3443-24-113-E2_ _ _ _ _17.4244327.61.7760.6004088282113D
FN 3443-32-115-E2_ _ _ _ _23.8325738.11.3010.43452115370115E
FN 3443-40-115-E2_ _ _ _ _29.3407146.51.0560.35757126453115E
FN 3443-48-115-E2_ _ _ _ _35.6488456.70.8690.29365143476115E
FN 3443-60-115-E2_ _ _ _ _44.36010470.80.6990.23667147634115F
FN 3443-80-115-E2_ _ _ _ _59.48013394.40.5210.17690198779115F
FN 3443-100-116-E2_ _ _ _ _73.61001631170.4210.142125276788116G
FN 3443-120-116-E2_ _ _ _ _88.71202081420.3490.118146322831116G

FN 3443-160-118-E2_ _ _ _ _

118.01602401880.2620.0891874121199118H

FN 3443-200-118-E2_ _ _ _ _**

147.32003202350.2100.0712044501022118H
FN 3443-240-118-E2_ _ _ _ _**177.32404032830.1750.0592695931292118H

*         Filter rating which does not require forced cooling or fan module
**       Filter rating which does not require RC damping module for rectifiers with EMI filter
***     Motor drive input current without harmonic filter
****   Typical losses @ 45°C, 380V, 60Hz and rated load power
***** In order to apply FN 3443 filters, motor drives have to be equipped with either DC-link choke or AC line choke. The minimum required inductance values are given in mH in the filter selection table. If neither DC-link choke nor AC line choke is present, or if the minimum mH rating is not fulfilled, FN 3443 filter must not be used. In this case, FN 3442 need to be chosen.

Filter power terminals

Terminal designation*

Screw thread

Flex wire AWGFlex wireScrew torque value


Max width**Frame size
cable lug
[mm2]  [Nm][lbs·in][mm]
110M314-220.4-2.50.54.47A
112M410-220.4-61.210.610B, C
113M66-180.75-16326.615D
115M81/0-810-50870.815E, F
116M83/0-810-95870.817G
118M103/0-500 kcmil95-2401088.535H

*  Recommended connector type: wire or cable lug for 110 to 113, only cable lug for 115 to 118
** To fulfill creepage/clearance acc. UL 61800-5-1 without additional protection (insulation). Creepage/clearance can vary depending on applicable standard and must be reviewed by customer. Creepage/clearance may be reduced when additional protection (insulation) is provided.

Filter signal and earth terminals

Terminal type

Screw thread

Screw torque value


Frame size
  [Nm][lbs·in]
SignalM3*0.54.4All
Earth (PE)M52.219.5A
Earth (PE)M6435.4B
Earth (PE)M6435.4C
Earth (PE)M8979.7D
Earth (PE)M8979.7E
Earth (PE)M1017150.5F
Earth (PE)M1017150.5G
Earth (PE)M1017150.5H

* Max width cable lug = 7 mm

Product selector

Filter configurations

E0XXXXX


- For rectifiers with DC-link choke

   
 
 
 

E0FAXRX


- For rectifiers with DC-link choke
  and with EMI filter

- Filters contain fan, aux. power
  supply and RC damper module
 

E0FAJRX and E2FAJRX


- For rectifiers with DC-link choke
  and with EMI filter

- Filters contain fan, aux. power
  supply, RC damper module and
  trap disconnect jumper

Mechanical data of IP 00 enclosure

Frame sizes A-F

Frame sizes G and H

Dimensions

Dimensions in [mm]Dimensions in [in]

Frame

Drill pattern

BaseVolumeDrill patternBaseVolume

R

STUXYZRSTUXYZ
A340120736030216018513.44.70.314.211.96.37.3
B405120742537018020615.94.70.316.714.67.18.1
C460150748343021022118.15.90.319.016.98.38.7
D5401801156049126025221.37.10.422.019.310.29.9
E6802201170563529031926.88.70.427.825.011.412.6
F7302501175268434034328.79.80.429.626.913.413.5
G9202801196086335338636.211.00.437.834.013.915.2
H1115390111150105346245643.915.40.445.341.518.218.0

Inlet air flow required for cooling

Frame size

Min air volume*

[m3/h]CFM [ft3/min]
A, B, C00
D12875
E204120
F, G408240
H612360

* External air flow required for filter configurations without embedded
   ventilation

Mechanical data of IP 20 enclosure

Frame sizes A-D

Frame sizes E-H

Dimensions

Dimensions in [mm]Dimensions in [in]

Frame

Drill pattern

BaseVolumeDrill patternBaseVolume

R

STUXYZRSTUXYZ
A340120736030216018513.44.70.314.211.96.37.3
B405120742537018020615.94.70.316.714.67.18.1
C460150748343021022118.15.90.319.016.98.38.7
D5401801156049126025221.37.10.422.019.310.29.9
E6802201170563529031926.88.70.427.825.011.412.6
F7302501175268434034328.79.80.429.626.913.413.5
G9202801196086335338636.211.00.437.834.013.915.2
H1115390111150105346245643.915.40.445.341.518.218.0

Inlet air flow required for cooling

Frame size

Min air volume*

[m3/h]CFM [ft3/min]
A, B, C00
D12875
E204120
F, G408240
H612360

* External air flow required for filter configurations without embedded
   ventilation

Headquarters, global innovation and development

Switzerland
Schaffner Group
Nordstrasse 11
4542 Luterbach
T +41 32 681 66 26
info@schaffner.com

To find your local partner within Schaffner‘s global network: www.schaffner.com

© 2018 Schaffner Group

The content of this document has been carefully checked and understood. However, neither Schaffner nor its subsidiaries assume any liability whatsoever for any errors or inaccuracies of this document and the consequences thereof. Published specifica-tions are subject to change without notice. Product suitability for any area of application must ultimately be determined by the customer. In all cases, products must never be operated outside their published specifications. Schaffner does not guarantee the availability of all published products. This disclaimer shall be governed by substantive Swiss law and resulting disputes shall be settled by the courts at the place of business of Schaffner Holding AG. Latest publications and a complete disclaimer can be downloa-ded from the Schaffner website. All trademarks recognized.

Sales and application centers

China
Schaffner EMC Ltd. Shanghai
T20-3 C, No 565 Chuangye Road,
Pudong district
201201 Shanghai
T +86 21 3813 9500
cschina@schaffner.com
www.schaffner.com.cn

Finland
Schaffner Oy
Sauvonrinne 19 H
08500 Lohja
T +358 10 567 2855
finlandsales@schaffner.com

France
Schaffner EMC S.A.S.
16-20 Rue Louis Rameau
95875 Bezons
T +33 1 34 34 30 60
F +33 1 39 47 02 28
francesales@schaffner.com

Germany
Schaffner Deutschland GmbH
Schoemperlenstrasse 12B
76185 Karlsruhe
T +49 721 56910
F +49 721 569110
germanysales@schaffner.com

India
Schaffner India Pvt. Ltd
REGUS WORLD TRADE CENTRE
WTC, 22nd Floor Unit No 2238, Brigade Gateway Campus, 26/1, Dr. Rajkumar Road Malleshwaram (W)
560055 Bangalore
T +91 80 67935355
indiasales@schaffner.com

Italy
Schaffner EMC S.r.l.
Via Ticino, 30
20900 Monza (MB)
T +39 039 21 41 070
italysales@schaffner.com

Japan
Schaffner EMC K.K.  
Taiju-Seimei Sangenjaya Bldg.
1-32-12, Kamiuma, Setagaya-ku
154-0011 Tokyo
T +81 3 5712 3650
F +81 3 5712 3651
japansales@schaffner.com
www.schaffner.jp

Singapore
Schaffner EMC Pte Ltd.
#05-09, Kg Ubi Ind. Estate
408705 Singapore
T +65 6377 3283
F +65 6377 3281
singaporesales@schaffner.com

Spain
Schaffner EMC España
Calle Caléndula 93, Miniparc III, Edificio E
El Soto de Moraleja, Alcobendas
28109 Madrid
T +34 917 912 900
F +34 917 912 901
spainsales@schaffner.com

Sweden
Schaffner EMC AB  
Östermalmstorg 1
114 42 Stockholm
T +46 8 5050 2425
swedensales@schaffner.com
www.schaffner.com

Switzerland
Schaffner EMV AG
Nordstrasse 11
4542 Luterbach
T +41 32 681 66 26
switzerlandsales@schaffner.com

Taiwan R.O.C.
Schaffner EMV Ltd.
20 Floor-2, No 97, Section 1, XinTai 5th Road
22175 XiZhi District New Taipei City 22175
T +886 2 2697 5500
F +886 2 2697 5533
taiwansales@schaffner.com
www.schaffner.com.tw

Thailand
Schaffner EMC Co. Ltd.
Northern Region Industrial Estate
67 Moo 4 Tambon Ban Klang
Amphur Muangg P.O. Box 14

51000 Lamphun
T +66 53 58 11 04
F +66 53 58 10 19
thailandsales@schaffner.com

United Kingdom
Schaffner Ltd.  
5 Ashville Way, Molly Millars Lane
Wokingham
RG41 2PL Berkshire
T +44 118 9770070
F +44 118 9792969
uksales@schaffner.com

USA
Schaffner EMC Inc.
52 Mayfield Avenue
Edison, New Jersey
T +1 732 225 9533
F +1 732 225 4789
usasales@schaffner.com
www.schaffnerusa.com

USA
Schaffner North America
6722 Thirlane Road
24019 Roanoke, Virginia
T +1 276 228 7943
F +1 276 228 7953

USA
Schaffner North America
823 Fairview Road
24382 Wytheville, Virginia
T +1 276 228 7943
F +1 276 228 7258