DATASHEET
Ecosine evo (5% THDi) FN 3440
Ecosine evo, 50 Hz Oberschwingungsfilter
2021
12 Apr 2021
Ecosine passiv
FN 3440: Ecosine evo, 50 Hz Oberschwingungsfilter
  • Der Industriestandard für 6-Puls-Gleichrichter und Motorantriebe
  • Filter für Diodengleichrichter mit Zwischenkreisdrossel
  • Erstklassige Teillastleistung
  • Kompakteste Bauform
  • Plug and Play, gebrauchsfertig
Technical specifications

Nominal operating voltage

3 x 380 VAC to 415 VAC ±10%

Frequenz

50 Hz ±1 Hz

Nominal motor drive input power rating

1.1 to 250 kW

Total harmonic current distortion THDi*

≤5% at rated power

Efficiency

>98% for rated voltage and power

Overload capability

1.6x rated current for 1 minute, once per hour

SCCR**

100 kA

High potential test voltage

P –> E 2160 VAC (1 s)

Overvoltage category

OV III (IEC 60664-1 / UL 61800-5-1)

Earthing System

TN, TT, IT

Protection category

IP 00, IP 20

Cooling

Internal fan cooling or external cooling***

Ambient temperature range

–25°C to +45°C fully operational
+45°C to +70°C derated operation****
–25°C to +85°C transport and storage

Design corresponding to

Filter: UL 61800-5-1, EN 61800-5-1
Chokes: EN 61558-2-20 or EN 60076-6

Flammability corresponding to

UL 94 V-2

MTBF @ 45°C/400 V (Mil-HB-217F)

>200,000 hours

Approvals & Compliances

(abhängig von der Filterkonfiguration)

Features and benefits

Schaffner ecosine harmonic filters represent an economical solution to the challenge of load-applied harmonics mitigation in three-phase power systems. With a plug-and-play approach and more compact dimensions than comparable products, they can be quickly installed and easily commissioned. They increase the reliability and service life of electric installations, help utilize electric sytem capacity better, and are the key to meet Power Quality standards such as IEEE 519. Ecosine filters reshape your distorted current back to the desired sinusoidal waveform. Schaffner ecosine filters can be applied to virtually any kind of power electronics with front-end six-pulse rectifiers, 3-phase diode or thyristor bridges, where harmonic current distortion needs to be reduced to defined limits.

Typical applications

  • Equipment with front-end six-pulse rectifier
  • Motor drives
  • Factory automation equipment
  • Water/wastewater treatment facilities
  • Fan and pump applications
  • HVAC installations
  • Mission-critical processes
  • DC fast chargers

Typical electrical schematic

(all configurable optional functionalities shown)

Filter selection table – IP 00 enclosure

Filter

Rated load power

Motor driveRated filter

Weight

Typical TerminalFrame 

@ 400 V/50 Hz

input currentinput current lossessize

[kW]

[Arms]***[Arms]

[kg]

[W]****
FN 3440-1-110-E0_ _ _ _ _*1.13.01.63761110A
FN 3440-2-110-E0_ _ _ _ _*2.25.53.261087110A
FN 3440-4-112-E0_ _ _ _ _*4.0105.9313135112B
FN 3440-6-112-E0_ _ _ _ _*5.5138.1717183112C
FN 3440-8-112-E0_ _ _ _ _*7.51611.121256112C
FN 3440-11-113-E0_ _ _ _ _112416.328287113D
FN 3440-15-113-E0_ _ _ _ _153222.232359113D
FN 3440-19-113-E0_ _ _ _ _193828.233343113D
FN 3440-22-115-E0_ _ _ _ _224532.548460115E
FN 3440-30-115-E0_ _ _ _ _306044.449570115E
FN 3440-37-115-E0_ _ _ _ _377554.860581115E
FN 3440-45-115-E0_ _ _ _ _459066.767783115E
FN 3440-55-115-E0_ _ _ _ _5511081.669858115E
FN 3440-75-116-E0_ _ _ _ _751501111181036116G
FN 3440-90-116-E0_ _ _ _ _901801341391166116G
FN 3440-110-118-E0_ _ _ _ _1102101641581365118H
FN 3440-132-118-E0_ _ _ _ _**1322601971761392118H

FN 3440-160-118-E0_ _ _ _ _**

1603202402021462118H

FN 3440-200-118-E0_ _ _ _ _**

2004003002101644118H
FN 3440-250-119-E0XXSXX2505303763241746119J

*      Filter rating which does not require forced cooling or fan module
**    Filter rating which does not require RC damping module for rectifiers with EMI filter
***   Motor drive input current without harmonic filter
****  Typical losses @ 45°C, 400 V, 50 Hz and rated load power

Filter power terminals

Terminal designation*

Screw thread

Flex wire AWGFlex wireScrew torque valueMax width**Frame size
cable lug
[mm2]  [Nm][mm]
110M314-220.4-2.50.57A
112M410-220.4-61.210B, C
113M66-180.75-16315D
115M81/0-810-50815E, F
116M83/0-810-95817G
118M103/0-500 kcmil95-2401035H
119M16350-750 kcmil185-4001048J

*  Recommended connector type: wire or cable lug for 110 to 113, only cable lug for 115 to 119
** To fulfill creepage/clearance acc. UL 61800-5-1 without additional protection (insulation). Creepage/clearance can vary depending on applicable standard and must be reviewed by customer. Creepage/clearance may be reduced when additional protection (insulation) is provided.

Filter signal and earth terminals

Terminal type

Screw thread

Screw torque valueFrame size
  [Nm]
SignalM3*0.5All
Earth (PE)M52.2A
Earth (PE)M64B, C
Earth (PE)M89D, E
Earth (PE)M1017F, G, H
Earth (PE)M1225J

* Max width cable lug = 7 mm

Filter selection table - IP 20 enclosure

Filter

Rated load power

Motor driveRated filter

Weight

Typical TerminalFrame 

@ 400 V/50 Hz

input currentinput current lossessize

[kW]

[Arms]***[Arms]

[kg]

[W]****
FN 3440-1-110-E2_ _ _ _ _*1.13.01.63861110A
FN 3440-2-110-E2_ _ _ _ _*2.25.53.261187110A
FN 3440-4-112-E2_ _ _ _ _*4.0105.9315135112B
FN 3440-6-112-E2_ _ _ _ _*5.5138.1719183112C
FN 3440-8-112-E2_ _ _ _ _*7.51611.123256112C
FN 3440-11-113-E2_ _ _ _ _112416.332287113D
FN 3440-15-113-E2_ _ _ _ _153222.236359113D
FN 3440-19-113-E2_ _ _ _ _193828.237343113D
FN 3440-22-115-E2_ _ _ _ _224532.553460115E
FN 3440-30-115-E2_ _ _ _ _306044.455570115E
FN 3440-37-115-E2_ _ _ _ _377554.866581115E
FN 3440-45-115-E2_ _ _ _ _459066.773783115E
FN 3440-55-115-E2_ _ _ _ _5511081.675858115E
FN 3440-75-116-E2_ _ _ _ _751501111261036116G
FN 3440-90-116-E2_ _ _ _ _901801341471166116G
FN 3440-110-118-E2_ _ _ _ _1102101641751365118H
FN 3440-132-118-E2_ _ _ _ _**1322601971941392118H

FN 3440-160-118-E2_ _ _ _ _**

1603202402191462118H

FN 3440-200-118-E2_ _ _ _ _**

2004003002271644118H
FN 3440-250-119-E2FASXX2505303763501746119J

*       Filter rating which does not require forced cooling or fan module
**     Filter rating which does not require RC damping module for rectifiers with EMI filter
***   Motor drive input current without harmonic filter
**** Typical losses @ 45°C, 400 V, 50 Hz and rated load power

Filter power terminals

Terminal designation*

Screw thread

Flex wire AWGFlex wireScrew torque valueMax width**Frame size
cable lug
[mm2]  [Nm][mm]
110M314-220.4-2.50.57A
112M410-220.4-61.210B, C
113M66-180.75-16315D
115M81/0-810-50815E, F
116M83/0-810-95817G
118M103/0-500 kcmil95-2401035H
119M16350-750 kcmil185-4001048J

*  Recommended connector type: wire or cable lug for 110 to 113, only cable lug for 115 to 119
** To fulfill creepage/clearance acc. UL 61800-5-1 without additional protection (insulation). Creepage/clearance can vary depending on applicable standard and must be reviewed by customer. Creepage/clearance may be reduced when additional protection (insulation) is provided.

Filter signal and earth terminals

Terminal type

Screw thread

Screw torque valueFrame size
  [Nm]
SignalM3*0.5All
Earth (PE)M52.2A
Earth (PE)M64B, C
Earth (PE)M89D, E
Earth (PE)M1017F, G, H
Earth (PE)M1225J

* Max width cable lug = 7 mm

Product selector

Table 1: Filter configurations if external air flow is available for cooling

(Filters do not contain fan and do not contain aux. power supply)

E0XXXXX

- For rectifiers without DC-link
  choke



E0XXJXX

- For rectifiers without DC-link
  choke

- Filters contain trap disconnect
  jumper

E0XXXRX

- For rectifiers without DC-link
  choke and with EMI filter

- Filters contain RC damper
  module

E0XXJRX

- For rectifiers without DC-link 
  choke and with EMI filter

- Contain RC damper module
  and trap disconnect jumper

Table 2: Filter configurations with embedded ventilation

(Filters contain fan and aux. power supply)

E0FAXXX and E2FAXXX

- For rectifiers without DC-link
  choke

- Filters contain fan, aux. power
  supply

E0FAJXX and E2FAJXX

- For rectifiers without DC-link
  choke

- Filters contain fan, aux. power
  supply and trap disconnect
  jumper

E0FAXRX and E2FAXRX

- For rectifiers without DC-link
  choke and with EMI filter

- Filters contain fan, aux. power
  supply and RC damper module
 

E0FAJRX and E2FAJRX

- For rectifiers without DC-link
  choke and with EMI filter

- Filters contain fan, aux. power
  supply, RC damper module and
  trap disconnect jumper

Table 3: Filter configurations if external aux. power supply for the fan is available

(Filters contain fan but do not contain aux. power supply, user should provide aux. power supply to the fan)

E0FXXXX and E2FXXXX

- For rectifiers without DC-link
  choke

- Filters contain fan
  

E0FXJXX and E2FXJXX

- For rectifiers without DC-link
  choke

- Filters contain fan and trap
  disconnect jumper

E0FXXRX and E2FXXRX

- For rectifiers without DC-link
  choke and with EMI filter

- Filters contain fan and RC
  damper module

E0FXJRX and E2FXJRX

- For rectifiers without DC-link
  choke and with EMI filter

- Contain fan, RC damper module
  and trap disconnect jumper

Table 4: 250 kW Filter configuration

E0XXSXX

- For rectifiers without DC-link
  choke

- Filters contain circuit breaker

E2FASXX

- For rectifiers without DC-link
  choke

- Filters contain fan aux. power
  supply and circuit breaker

Mechanical data of IP 00 enclosure

Frame sizes A-F

Frame sizes G and H

Frame size J

Dimensions

Frame   

Drill pattern

Base Volume

 

  

[mm]

 

[mm]

 

[mm]

 

R S

T

U

 X

Y

Z

A

             340             120

7

                  360

              302

             160

             185

B

405 120

7

425

370

180

206

C

460 150

7

483 430

210

221

D

540 180

11

560

491 260

252

E

680 220

11

705 635 290

319

F

730 250

11

752

684 340

343

G

920 280

11

960

863 353

386

H

1115 390

11

1150

1053 462

456

J 1348 480 11 1400 1300

550

555

 

 

 

Inlet air flow required for cooling

Frame size

Min air volume*

[m3/h]
A, B, C0
D128
E204
G408
H612
J816

* External air flow required for filter configurations without embedded
   ventilation

Mechanical data of IP 20 enclosure

Frame sizes A-D

Frame sizes E-H

Frame size J

Dimensions

Frame

Drill pattern

BaseVolume

 

[mm]

 

[mm]

 

[mm]

 

RS

T

U

 X

Y
Z

V

A

             340            120

7

                  360

              302

             160

             185

                   

B

405120

7

425

370

180

206

C

460150

7

483430

210

221

D

540180

11

560

491260

252

E

680220

11

705635290

319

F

730250

11

752

684340

343

 

G

920280

11

960

863353

386

 

H

1115390

11

1150

1053462

456

 

J13484801114001300

550

555

1455

 

 

 

Inlet air flow required for cooling

Frame size

Min air volume*

[m3/h]
A, B, C0
D128
E204
G408
H612
J816

* External air flow required for filter configurations without embedded
   ventilation

Headquarters, global innovation and development

Switzerland
Schaffner Group
Industrie Nord
Nordstrasse 11e
4542 Luterbach
T +41 32 681 66 26
info@schaffner.com

www.schaffner.com

© 2021 Schaffner Group

The content of this document has been carefully checked and understood. However, neither Schaffner nor its subsidiaries assume any liability whatsoever for any errors or inaccuracies of this document and the consequences thereof. Published specifications are subject to change without notice. Product suitability for any area of application must ultimately be determined by the customer. In all cases, products must never be operated outside their published specifications. Schaffner does not guarantee the availability of all published products. This disclaimer shall be governed by substantive Swiss law and resulting disputes shall be settled by the courts at the place of business of Schaffner Holding AG. Latest publications and a complete disclaimer can be downloaded from the Schaffner website. All trademarks recognized.

PQ sales

Switzerland
Schaffner Power Quality
Nordstrasse 11e
4542 Luterbach
T +41 32 681 66 80
pqsales@schaffner.com

China
Schaffner Power Quality China
T20-3 C, No 565 Chuangye Road
Pudong district
201201 Shanghai
T 021-38139500-2412
pqsales@schaffner.com

Singapore
Schaffner Power Quality APAC
#05-09, Kg Ubi Ind. Estate
Blk 3015A Ubi Road 1
408705 Singapore
T +65 6460 4166
pqsales@schaffner.com